Magnum Products, LLC Print logo Handheld logo

Skip navigation

More Information

Manuals

    Tech. Specs.

    ALWAYS check for updated parts information before placing a parts order.

    Literature / Sales

    MMG 175 Interim Tier IV Mobile Generator

    Moving Forward - Keeping Pace with Emissions Technology

    Reliable engine performance and reduced emissions walk hand in hand in Magnum Generator models as we keep pace with emissions technology meeting required emissions regulations. Magnum introduced the MMG 175 generator, the first of many Interim Tier IV models powered by an Interim Tier IV John Deere PowerTech engine.

    Making the Difference - DOC/DPF Exhaust Filter

    The MMG175 is powered by a John Deere PowerTech engine which utilizes a catalyzed exhaust filter that contains a Diesel Oxidation Catalyst (DOC) and a Diesle Particulate Filter.(DPF) The DOC reacts with exhaust gases to reduce the carbon monoxide, hydrocarbons and some particulate matter(PM). The downstream DPF traps and holds the remaining PM, which are oxidized within the DPF through a continuous process called passive regeneration.

    Features

    Reliable

    • Voltage regulation is plus or minus 1%
    • 342 gallon fuel capacity standard for 29 hours of run time
    • Air filter condition indicator on control panel
    • 2 year - 2,000 hour warranty
    • Low coolant shutdown

    Durable

    • White aluminum textured powder coat enclosure, sound attenuated baffles and insulation to reduce noise, 68 dBA at prime
    • Fully lockable enclosure with stainless steel exterior hardware
    • Industrial strength steel skid frame and dual axle trailer
    • Central lift structure and convenient ladder on center of generator

    Microprocessor Controlled for Safety

    • Engine & generator protection with our advanced Magnum Digital Controller (MDC)
    • Fuel pressure monitoring
    • Oil pressure monitoring
    • Coolant monitoring
    • Battery voltage monitoring
    • Gen voltage monitoring
    • Overspeed monitoring
    • Over/under current monitoring
    • Generator over/under frequency monitoring

    Easy to Use

    • Voltage selector switch (single phase & two 3-phase)
    • Electronic governor
    • Lugs and lug box safety switch, if cover is opened circuit breaker is tripped
    • Several convenience outlets with individual breakers
    • Durable external emergency E-stop switch
    • External fuel fill with lockable cap
    • Automatic remote start capable, located on control panel
    Warranty Responsibility: It is the responsibility and obligation of the purchaser to thoroughly read and understand the Magnum warranty prior to purchasing equipment. Failure to read and comprehend the warranty policy does not expose Magnum to any liabilities over and above the stated warranty bond. If you have any questions or need clarification of warranty details please contact warranty@m-p-llc.com or call technical support at 800.926.9768.

    Specifications

    Output CSA Certified

    3 Phase - Standby kW (kVA) 153 (191)
    Amps 480V (208V) 230 (530)
    3 Phase - Prime kW (kVA) 138 (172)
    Amps 480V (208V) 207 (477)
    1 Phase - Standby kW (kVA) 125 (125)
    Amps 240V 521
    1 Phase - Prime kW (kVA) 120 (120)
    Amps 240V 500
    AC Voltage 1-phase 120, 139, 208, 220, 240, 277
    AC Voltage 3-phase 208, 220, 440, 480
    Frequency Hz 60
    Power Factor 1.0 (1 Phase) / .8 (3 Phase)
    Generator - Brand / Type / Insulation Marathon / Brushless / H
    Sound (dB(A) 23 ft @ prime) 68

    Size and Weight

    Skid Mounted - L x W x H in (m) 144 x 50 x 77
    Dry Weight lbs (kg) 6604 (2996)
    Operating Weight lbs (kg) 9032 (4097)
    Trailer Mounted - L x W x H in (m) 210 x 86 x 93
    (5.33 x 2.18 x 2.36)
    Dry Weight lbs (kg) 8000 (3629)
    Operating Weight lbs (kg) 10428 (4730)

    Engine

    Type Interim Tier IV
    Brand John Deere PE6068HFG94
    Aspiration Turbo
    Power - Prime @ 1800 rpm hp (kWm) 217 (162)
    Displacement cubic in (L) 415 (6.8)
    Cylinders 6
    Speed rpm 1800
    Fuel Consumption - Prime gph (Lph) 10.9 (41.3)

    Capacities

    Fuel Tank gal (L) 342 (1295)
    Approximate Run Time hrs 29
    Coolant qt (L) 31.5 (29.8)

    Electrical Distribution

    Battery - 12V 1 - 12V 1000 CCA Wet Cell
    Main Circuit Breaker Size A 700
    Voltage Selection 3 Position Switch (lockable)
    Voltage Regulation +/-1%
    120V - 20A GFI Duplex Outlets - qty 2
    240V - 30A Twist Lock Outlets - qty N/A
    240V - 50A Twist Lock Outlets - qty 3

    Trailer

    Number of Axles 2
    Capacity - Axle Rating lbs (kg) 6000 (2722)
    Tire Size in 16
    Brakes Surge
    Hitch 3" Ring
    Maximum Tire Pressure psi 75

    Options

    Powertrain (Engine/Gen) • Engine Heater (Kim Hotstart)
    • 60/40 Coolant
    • Super Start Generator
    • PMG Generator
    • Fuel Transfer Pump
    Controls • Battery Disconnect, Lockable
    • Battery Charger, 2 Amp
    • 4 Position Phase Switch
    • Buck Transformer Kit
    • Cam Locks
    Cabinet/Fuel Tank • 36 hr Fuel Tank
    • Double Wall Standard Fuel Tank
    • Containment
    • Interior Cabinet Light
    • Control Panel Light
    • Auxiliary Strobe/Audible Indication
    • Fire Extinguisher
    Trailer • 2 5/16" Ball
    • Electric Brakes
    • Spare Tire/Wheel Kit